Search
enLanguage
Schneider ac Contactor LC1D25BD
video
Schneider ac Contactor LC1D25BD

Schneider ac Contactor LC1D25BD

LC1C25BD
Brand Name: Schneider
Product Name: Contactor
Type: LC1D25BD
Electricity Type: DC
Lead Time: in stock
Shipping Method: DHL/ TNT/ FEDEX/ AIR/ OCEAN
Payment Method: Wire Transfer/ West Union/ PayPal/ Alipay
Send Inquiry
Product Details ofSchneider ac Contactor LC1D25BD
Schneider DC Magnetic contactor LC1D25BD 25A 24VDC 3P

LC1D25BD-banner

Introduction
LC1D25BD is a powerful contactor designed for a wide range of industrial applications. It has a rated voltage of 240V and a rated current of 25A, making it suitable for various uses. With a built-in thermal overload relay, the contactor is protected against overloading and overheating, ensuring its durability and longevity. LC1D25BD is highly customizable and can be easily configured to meet specific customer requirements. Its modular design allows for easy modifications, making it a versatile choice for industrial automation, adapting to different processes and machinery effortlessly.
LC1D25BD
Features

 

  • The LC1D25BD improves efficiency and reliability in industrial applications. It enables precise control of electrical currents, reducing the risk of equipment failure due to voltage fluctuations or other electrical issues. Additionally, the contactor reduces energy consumption, contributing to a more sustainable and cost-effective operation.
  • The built-in thermal overload relay ensures the contactor's protection and safeguards machinery and equipment. This feature provides peace of mind to operators, allowing them to focus on other critical aspects of their work, knowing that the LC1D25BD is reliable.
  • Moreover, the modularity of the LC1D25BD enhances adaptability to various applications. This versatility allows for greater flexibility in designing and optimizing industrial processes, resulting in improved productivity and efficiency.

 

 

Products Description
 
Specification of schneider DC Schneider magnetic contactor LC1D25BD:

 

Range of product
TeSys D
TeSys Deca
Product or component type
Contactor
Device short name
LC1D
Contactor application
Motor control
Resistive load
Utilisation category
AC-4
AC-3
AC-1
AC-3e
Poles description
3P
Motor power kW

5.5 kW at 220...230 V AC 50/60 Hz (AC-3)

11 kW at 380...400 V AC 50/60 Hz (AC-3)

11 kW at 415...440 V AC 50/60 Hz (AC-3)

15 kW at 500 V AC 50/60 Hz (AC-3)

15 kW at 660...690 V AC 50/60 Hz (AC-3)

5.5 kW at 400 V AC 50/60 Hz (AC-4)

5.5 kW at 220...230 V AC 50/60 Hz (AC-3e)

11 kW at 380...400 V AC 50/60 Hz (AC-3e)

11 kW at 415...440 V AC 50/60 Hz (AC-3e)

15 kW at 500 V AC 50/60 Hz (AC-3e)

15 kW at 660...690 V AC 50/60 Hz (AC-3e)

Motor power hp

3 hp at 230/240 V AC 50/60 Hz for 1 phase motors

2 hp at 115 V AC 50/60 Hz for 1 phase motors

7.5 hp at 230/240 V AC 50/60 Hz for 3 phases motors

15 hp at 460/480 V AC 50/60 Hz for 3 phases motors

20 hp at 575/600 V AC 50/60 Hz for 3 phases motors

7.5 hp at 200/208 V AC 50/60 Hz for 3 phases motors

Pole contact composition
3 NO
Contact compatibility
M4
Protective cover
With
Auxiliary contacts type
type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-
type mirror contact 1 NC conforming to IEC 60947-4-1
Auxiliary contact composition
1 NO + 1 NC
[Ui] rated insulation voltage

Power circuit: 690 V conforming to IEC 60947-4-1

Power circuit: 600 V CSA certified

Power circuit: 600 V UL certified

Signalling circuit: 690 V conforming to IEC 60947-1

Signalling circuit: 600 V CSA certified

Signalling circuit: 600 V UL certified

[Uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947
Overvoltage category
III
[Ith] conventional free air thermal current

10 A (at 60 °C) for signalling circuit

40 A (at 60 °C) for power circuit

Irms rated making capacity
140 A AC for signalling circuit conforming to IEC 60947-5-1

250 A DC for signalling circuit conforming to IEC 60947-5-1

450 A at 440 V for power circuit conforming to IEC 6094

Rated breaking capacity
450 A at 440 V for power circuit conforming to IEC 60947
Control circuit type
DC standard
Coil technology
Built-in bidirectional peak limiting diode suppressor
Control circuit voltage limits

0.1...0.25 Uc (-40…70 °C):drop-out DC

0.7...1.25 Uc (-40…60 °C):operational DC

1...1.25 Uc (60…70 °C):operational DC

Average impedance
2 mOhm - Ith 40 A 50 Hz for power circuit
Power dissipation per pole

3.2 W AC-1

1.25 W AC-3

1.25 W AC-3e

Minimum switching current
5 mA for signalling circuit
Minimum switching voltage
17 V for signalling circuit
Non-overlap time

1.5 ms on de-energisation between NC and NO contact

1.5 ms on energisation between NC and NO contact

Maximum operating rate
3600 cyc/h 60 °C
Inrush power in W
5.4 W (at 20 °C)
Hold-in power consumption in W
5.4 W (at 20 °C)
Insulation resistance
> 10 MOhm for signalling circuit
Tightening torque

Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm

Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2

Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm

Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver Philips No 2

Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2

Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver pozidriv No 2

Mounting support
Plate
Rail
Mechanical durability
30 Mcycles
Safety reliability level

B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1

B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1

Operating altitude
0...3000 m
Compatibility code
LC1D
Product certifications

LROS (Lloyds register of shipping)

BV

GL

CCC

RINA

GOST

CSA

DNV

UL

UKCA

 
Condition of environment of schnieder DC magnetic contactor be used:

 

Climatic withstand

conforming to IACS E10 exposure to damp heat

conforming to IEC 60947-1 Annex Q category D exposure to damp heat

Permissible ambient air

temperature around the device

-40…60 °C

60…70 °C with derating

Fire resistance
850 °C conforming to IEC 60695-2-1
Mechanical robustness

Vibrations contactor open (2 Gn, 5...300 Hz)

Vibrations contactor closed (4 Gn, 5...300 Hz)

Shocks contactor closed (15 Gn for 11 ms)

Shocks contactor open (8 Gn for 11 ms)

 
Dimension of schneider DC magnetic contactor LC1D25BD:
 
Height
85 mm
Width
45 mm
Depth
101 mm
Net weight
0.53 kg
 
 
Certification

 

Certificate of Authorized Distributor of Schneider Electrics

 

 

product-533-784

 

UL certificate for Schneider Electrics

 

Schneider UL Certification

 

TAF certification for Schneider Electrics

 

Schneider TAF Certification

 

Shipping Method

 

unnamed

DHL Exrepss

3~7 days delivery

unnamed

FEDEX Express

3~7 days delivery

istockphoto-501294660-612x612

AIR Transport

Heavy cargo ship via air with high efficiency.

illustration-6-101-1024x535

OCEAN Transport

Heavy cargo ship via sea with competitiive shipping cost.

 

 

Payment Methods

 

1

Wire Transfer (T/T)

2

PayPal / Alipay

3

West Union

 

Hot Tags: schneider ac contactor lc1d25bd, schneider ac contactor lc1d25bd suppliers, 16 amp 2 pole contactor, dc contactor 24v, hpl contactor, 32a contactor, contactor 230v, clapper type contactor

Next
No Information

Send Inquiry

(0/10)

clearall